Skip to content

The source for calibration professionals

PrimeTest 250 PAT Testing Kit

 
The PrimeTest 250 PAT testing kit is based around the most comprehensive manual portable appliance tester on the market, featuring 3-phase leakage, RCD trip time, touch current and PE conductor current tests.

PATGuard Elements software (optional) enables fast manual data-entry for record-keeping of all test results including a full test history against each appliance, and invoice generator - ideal for the efficient running of your PAT business.

The PATBag includes:
  • PrimeTest 250 portable appliance tester
  • Rugged and lightweight purpose-made PATBag carry case with compartments for all of your PAT accessories and labels
  • Online PAT training course with exam and personalised certificate
  • Seaward Guide to Portable Appliance Testing, a handy PAT reference look-up card
  • PAT Register and Test record for keeping a record of results
  • 500 Pass labels
  • 500 Fail labels
  • 110V adaptor
  • Quick start video guide
  • Seaward Business Builder CD - everything you need to know to start a PAT testing business
*Please note the PrimeTest 250 portable appliance tester does not have a backlight.

Earth continuity

Output Current 200mA
Test Voltage (o/c) 9V DC nominal
Test Duration (Class I Test) 2s nominal
Display Range 0.01ohm to 19.99ohm
Pass Value (Class I Test) 0.2ohm

Insulation resistance

Test Voltage 250/500VDC @1mA nominal, < 2mA (s/c)
Test Duration (Class I or II) 2s nominal
Display Range 0.01Mohm to 19.99Mohm
Pass Value 1.0 Mohm Class I 2.0 Mohm Class II

Equivalent leakage

Test Voltage 40V Nominal AC 50Hz Open Circuit
Test Duration 2s nominal
Display Range 0.1mA to 19.99mA
Pass Value 0.75mA CLI / 0.25mA CL II

IEC lead test

Test voltage 5V DC nominal
Test Duration Time for test (2s max)
Test Live / Neutral Checks for o/c, s/c and crossed

Protective Conductor Current

Test Voltage Supply Voltage, max current 13A
Test Duration 30s maximum
Display Range 0.15mA to 9.99mA
Pass Value 0.75mA/3.5mA (user selectable with 0.75mA as default)

Touch current

Test Voltage Supply Voltage, max current 13A
Test Duration 30s maximum
Display Range 0.10mA to 5.00mA
Pass Value 0.25mA

3 phase differential leakage current

*Requires 3 phase adaptor accessory
Test Voltage 3 phase supply voltage
Test Duration continuous measurement
Display Range 0.10mA to 9.99mA
Pass Value 3.5mA

RCD trip time

Test Voltage Mains supply voltage
Test Current 10mA / 30mA rms sinusoidal
Test Current Phase 0°/180° auto switched on alternate tests
Measuring Range 0ms - 500ms
Pass Value 200ms

Power Socket Check

Input voltage range 225 - 254V AC max current 13A UK
Measurement range 50V to 250V
Indicates measured voltage and pass/fail for Line to earth, line to neutral, neutral to earth

PATGuard Elements System Requirements:

IBM Compatible PC
Processor Speed 500Mhz or higher
Microsoft Windows XP/VISTA/Windows 7
32 & 64 bit operating systems
512Mb RAM
150Mb available hard disk space
Colour monitor with 32 bit colour or greater video card
CD ROM drive
Licences: PATGuard Elements Licence (387A912) Part number: 345A927