Time Electronics 5069
A precision instrument suitable for calibrating and testing general purpose insulation testers and megohmmeters with test voltages up to 10kV.
It is constructed in a high strength co-polymer plastic case and is powered by a rechargeable battery. This ensures full isolation from the mains and prevents stray leakage.
The insulation tester being calibrated can be tested for open circuit voltage and short circuit current. These are displayed on the digital meter mounted on the front panel. The insulation resistance is provided by a precision 4 dial decade resistance bank which can be set to a maximum of 99.99GΩ with additional resistance values of 100kΩ, 200kΩ, 500kΩ, 1MΩ, 2MΩ and 5MΩ which can be switched in as required.
Rugged and portable, the 5069 is ideal for site calibration work. Also available is the 5068 InsCal Insulation Test Calibrator, 2.5kV version, and for additional electrical testing capabilities the 5030 calibrator is an excellent solution.
It is constructed in a high strength co-polymer plastic case and is powered by a rechargeable battery. This ensures full isolation from the mains and prevents stray leakage.
The insulation tester being calibrated can be tested for open circuit voltage and short circuit current. These are displayed on the digital meter mounted on the front panel. The insulation resistance is provided by a precision 4 dial decade resistance bank which can be set to a maximum of 99.99GΩ with additional resistance values of 100kΩ, 200kΩ, 500kΩ, 1MΩ, 2MΩ and 5MΩ which can be switched in as required.
Rugged and portable, the 5069 is ideal for site calibration work. Also available is the 5068 InsCal Insulation Test Calibrator, 2.5kV version, and for additional electrical testing capabilities the 5030 calibrator is an excellent solution.
Technical Specifications
General Specifications
Resistance | 10GΩ, 1GΩ, 100MΩ, 10MΩ decade ranges. |
---|---|
Fixed Values | 5MΩ, 2MΩ, 1MΩ, 500KΩ, 200KΩ, 100KΩ. |
Resistance Accuracy | 100kΩ to 5MΩ = 1%. 10MΩ to 10GΩ = 1%. 10GΩ to 100GΩ = 5%. |
Resistance Temperature Coefficient | Less than 250ppm per °C |
Open Circuit Voltage Measure | 0 to 2kV range, accuracy 1% of f/s. 0 to 10kV range, accuracy 2% of f/s. |
Voltage Display | 1.999kV full scale, and 10kV full scale. |
Short Circuit Current Measure | 0 to 2mA range and 0 to 20mA range = 1% of f/s accuracy. |
Current Display | 1.999mA full scale, and 19.99mA full scale. |
General Specifications
Power | Internal battery, 6V re-chargeable NiCad, >150hrs between charges. |
---|---|
Dimensions | W406 x H175 x D330mm |
Weight | 4.4kg |
Supplied With | Safety connection leads with bare end to allow custom probes (10kV rated), 4mm 5kV test lead set, wallet to carry test leads, and mains charger. |
Optional Extras | Calibration certificates traceable NPL and UKAS |
Country of Origin | UK |